Machine Model: GENIND

 

Model Equations and/or Block Diagrams

Parameters:

Ls Synchrounous reactance, (pu > 0)
Lp Transient reactance (pu, > 0)
Ra Stator resistance, pu
Tpo Transient rotor time constant, sec
H Inertia constant, sec
D Damping factor, pu
SE1 Saturation factor at E1
SE2 Saturation factor at E2
Acc Acceleration factor for initialization
Lpp Sub-transient reactance (pu, > 0)
Ll Stator leakage reactance (pu, > 0)
Tppo Sub-transient rotor time constant, sec
ndelt Model Parameters\ndelt
wdelt Model Parameters\wdelt
VT Voltage threshold for tripping, pu
TV Voltage trip pickup time, sec